 MECO MASTERedge Feed Water Level Control

 


The feed water level is maintained with a PID control loop. The proper feed water level is maintained in the evaporator even under fluctuating feed water pressure conditions. The PID control loop senses the actual level and adjusts the flow rate of feed water up or down to maintain the level at the desired point.

Integrated into the generator, this system provides precise control without the use of space-consuming external break tank / feed pump systems or external regulators. All loop parameters can be viewed from the unit's operator interface.

The level transmitter (LT) senses the feed water level in the evaporator and transmits a corresponding 4-20 ma signal to the unit's PLC-based control system. The PLC feed water level logic (LIC) monitors this input signal and determines the error between the actual level in the evaporator and the desired level.

If the actual level is higher than the desired level, an output signal from the PLC will close the feed water control valve to reduce the feed water flowrate to the evaporator. If the actual level is lower than the desired level, an output signal from the PLC will open the feed water control valve to increase the feed water flowrate to the evaporator.

The output signal from the PLC will take into consideration the magnitude of the error, the length of time that the error has existed, and the rate at which the error is changing to provide the most accurate control possible.

The 4-20 ma output signal from the PLC is sent to the current to pressure transducer (LY), which converts the electrical signal to a corresponding 3-15 psig pneumatic signal. The pneumatic signal is sensed by the feed water control valve positioner. The positioner also senses the position of the valve stem and maintains a valve position corresponding to the signal from the PLC, regardless of line pressure forces acting on the valve.


click here to enlarge.

 

   < Back to Process Control Basics

 


 

Design Features

How It Works

Size and Utilities

Control Technology

>

 

Process Controls


>

 

MASTERedge Feedwater Level Control


>

 

MASTERedge
Pure Steam
Pressure Control



Technical Specs

MASTERedge

MASTERsupport

FAQs

 


  



Contact Us  |  Site Map  |  Terms & Conditions  |  Privacy Policy  |  MECO.com  |  Employment  |


12505 Reed Road, Suite 100, Sugar Land, TX 77478
281.276.7600 (p) 800.421.1798 281.313.0643 (f)

© 2004 MECO, All Rights Reserved. This website requires Flash. Click Here if you don't have Flash.